产品
WISE
韩国
    Explosion proof differential pressure switch Model P991 series

    8635

    85

    128

    联系供应商
    收藏 点赞

    描述

    目录

    视频

    Service intended
    P991 explosion proof type differential switch series are bellows type, and these are primarily used for detecting the draft pressure in thermal power plants.
    Fluid
    Air and gas
    Repeatability
    ±1.5% of fullscale
    Dead band
    Fixed. 0.25 ~ 0.8 kPa or less
    Differential pressure range (kPa)
    0 ~ 4 kPa to 0 ~ 20 kPa
    Static pressure
    500 kPa
    Working temperature
    ●Ambient : -20 ~ 65°C 
    ●Fluid : Max. 60°C
    Degress of protection
    EN60529/IEC529/IP65

    Material
    ●Pressure connection : 316SS 
    ●Bellows : Stainless steel (316L SS) 
    ●Gasket : PTFE
    Case and cover
    ●ALDC 12.1 
    ●Silver gray painted aluminium
    Mounting
    Surface wall mounting
    Setpoint adjustment
    Internal
    Process connection
    ¼" NPT (F)
    Conduit connection
    ¾" PF (F)
    Operating environment
    Hazardous area refer to the explosion-proof item for information
    Optional
    ●3-way manifold valve 
    ●5-way manifold valve
    Contact type
    ●One SPDT 
    ●One DPDT
    Contact rating
    ●AC 125 V / 250 V, 15 A and DC 30 V, 2 A 
    DC 125 V, 0.5 A for resistance load 
    ●AC 125 V / 250 V, 15 A and DC 30 V, 1 A 
    DC 125 V, 0.05 A for Inductive load
    Approval by standard
    KOSHA 12-AV2B0-0057
    • Explosion proof differential pressure switch Model P991 series.pdf